VFD-L-1 - Drive : Selec

Brief Specifications

AC Input Voltage Range Single Phase: 230 V AC
Frequency Range 50/60 Hz
Control Mode Space vector PWM (SVPWM)-based scalar control
Frequency Control Range 0.1 to 400 Hz
Acc./Dec. Time 0.1 to 999.9 sec., four acceleration and deceleration time settings available
Overload Capacity 150% for 1 min, 180% for 10 sec., 200% for 1 sec.
Protection functions Over voltage, Under voltage, Over current, Over temperature, Over load, Under current and Output short circuit
Ingress Protection IP20
Working Temperature -10 to +55 °C
Ambient humidity <90%, No condensation
Installation location Indoor, <1000m altitude above sea level

Product Variants

Product CodeDescriptionOutput CurrentCertification
VFD-L-1-002-230V1 phase input 230V AC, 3 phase output 0 to rated Input voltage 0.25HP/0.2kW, General purpose series (4 DI, 2 AI, RS485, 1 RO SPDT, 1 TO)1 A---
VFD-L-1-005-230V1 phase input 230V AC, 3 phase output 0 to rated Input voltage 0.5HP/0.4kW, General purpose series (4 DI, 2 AI, RS485, 1 RO SPDT, 1 TO)2.5 A ---
VFD-L-1-010-230V1 Phase 230VFD-L-1-010-230VV AC INPUT, 3 Phase 0 to 230V AC OUTPUT, 1 HP/0.75 kW 5 A---