Product Details

Brief Specifications

Measuring ParameterUnder Current, Over Current, Current Asymmetry Monitoring
Electrical Connection1Ø-2W, 3Ø-3W, 3Ø-4W
Display3 Digits Liquid Crystal Display with Backlight
CT SettingCT Primary: 1A / 5A – 999A, CT Secondary: 1A / 5A (selectable)
Time RangesPower ON Delay: 0.5–99.9sec, Trip time delay: 0–99.9sec,Recovery Time Delay: 0–99.9sec (In Auto Reset Mode), Response Time: <200ms
AccuracyCurrent: ±1% of Setting ± 2 digits, Time Setting Accuracy: ±5% of Setting ±200ms
Output Contact1 C / O (SPDT)
Output RatingNO: 5A@250V AC, NC: 3A@250V AC
Supply Voltage230V AC (±15%)
Size35 mm
Mounting TypeDIN Rail Mount
CertificationCE

Product Variants

No Product Variant Available