TPS50 - Panel Mount Power Supplies : Selec

Brief Specifications

Input Voltage 90 - 264 VAC (127- 373 VDC)
Frequency Range 47 - 63 Hz
Inrush Current < 45 Amps; Measured at 230 VAC, 25°C Ambient, Cold start
Output Voltage 24V
Output Power 50 W
Voltage Tolerance ± 1 %
Line Regulation ± 1 %
Load Regulation ± 1 %
Turn On Time < 3 sec ; at full load
Hold Up Time ≥ 60 ms at 230 VAC & ≥ 10 ms at 115 VAC, Full load
Rise Time < 100 ms
Overload Protection > 110 % of rated output current; Hiccup mode; Autorecovery type
Output Short Circuit Protection Hiccup mode when output is shorted; Autorecovery type
Operating Temperature -25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C,
-25°C to 0°C startup is guaranteed with specification deviation ( Output ripple can be more than 10 % of the output voltage. )
Storage Temperature -40°C to +85°C
Cooling Natural Convection Cooled
Humidity 5 to 95 % RH, Non condensing
Altitude 2000 m
Dimension 99 x 82 x 30 mm (L x W x H)
Weight < 230 gms
Mounting Table Top

Product Variants

Product CodeDescriptionCertification
TPS50-2450 W, 24 V / 2.2 A Table Top Power Supply in metal bodyCE